Dubai, United Arab Emirates, serving the GCC+971 52 249 5822 · info@hiks.org
Resources / Technical Insights

Engineering guides written by people who build panels for a living.

Practical, standards-referenced answers to the questions consultants, contractors and facility engineers ask us most. No marketing, just the engineering.

IEC 61439-2

Forms of Separation Explained: Choosing Between Form 1 and Form 4b

What the forms actually separate, what each costs you in space and money, and how to specify without over-buying.

9 min read
Protection

Why Your Main Breaker Trips First, Selectivity, Explained Properly

The anatomy of a discrimination failure, and how a coordination study turns a blackout into a single tripped feeder.

10 min read
Testing

The FAT Witness Checklist: What to Verify Before You Accept an LV Panel

The complete inspection sequence, what to open, what to torque-check, what to ask for in writing.

8 min read
Design, GCC

Busbar Sizing and Temperature Rise at 50 °C: Why Catalogue Ratings Fail in the Gulf

Derating, ventilation and verification when your switchroom runs hotter than the standard assumes.

9 min read
Critical Power

AMF vs ATS: Specifying Generator Changeover Without the Confusion

Two terms used interchangeably, two different scopes, and the specification gaps that cause failed outage tests.

8 min read
IEC 61439-2 · Design

Forms of Separation Explained: Choosing Between Form 1 and Form 4b

HIKS STAR Engineering9 min read

Few specification clauses cause as much silent over-spending, or as much quiet risk, as the form of separation. It is written into nearly every LV switchboard specification in the GCC, frequently copied from the last project, and rarely re-examined against what the installation actually needs.

What separation actually does

IEC 61439-2 defines forms of internal separation as the degree to which an assembly is divided internally by barriers or partitions. The purpose is twofold: protection against contact with live parts of adjacent functional units during work on the assembly, and limitation of the consequences of an internal fault, an arc in one compartment is far less likely to propagate into the next.

The forms answer three separation questions: are the busbars separated from the functional units? Are the functional units separated from each other? And are the external cable terminals separated from the functional units?

FormWhat is separatedTypical application
Form 1No internal separation, enclosure protection onlySmall DBs, non-critical plant
Form 2bBusbars separated from functional units (terminals included)SMDBs, light commercial
Form 3bAs 2b, plus functional units separated from each otherMCCs, mid-size MDBs
Form 4aAs 3b, plus terminals in the same compartment as their unitMain boards, hospitals
Form 4bFull separation, terminals in their own compartments or glanded separatelyData centres, critical MDBs

What higher forms cost you

Each step up adds barriers, metalwork and, critically, space. In our build practice, moving the same feeder schedule from Form 2b to Form 4b typically reduces usable mounting height per section by ten to fifteen percent and can add a full section to the lineup. It also adds assembly hours and material, which is why a Form 4b board can cost meaningfully more than the identical schedule in Form 3b.

The question is never "what is the best form", it is what work will be done on this board while it is live. If a feeder will ever be isolated, terminated or maintained while the rest of the board stays energised (hospitals, data rooms, process plants that cannot stop), high separation pays for itself the first time. If the whole board can be shut down for any intervention, Form 4b is often specification inertia.

Specifier's shortcut: match the form to the operating philosophy, not to the building type. A shopping mall with a full-shutdown maintenance regime needs less separation than a small factory that can never stop production.

Three clauses to write into your next specification

  1. State the form and the sub-form letter (3b, 4a, 4b), "Form 4" alone is ambiguous and will be priced differently by every bidder.
  2. State whether separation is achieved by barriers or by insulated coverings; the two are not equivalent for maintenance access.
  3. Require the manufacturer to demonstrate the form at FAT with covers removed, separation is visible, so witness it.
Unsure which form your project actually needs?Ask our engineers
Protection & Coordination

Why Your Main Breaker Trips First, Selectivity, Explained Properly

HIKS STAR Engineering10 min read

The call always sounds the same. A fault on one small circuit, a failed motor, a damaged cable, and instead of one feeder tripping, the main incomer opens and the whole facility goes dark. The fault was worth one machine. The outage cost the building.

What selectivity means

Selectivity (discrimination) is the property of a protection scheme whereby, for any fault, only the protective device immediately upstream of the fault operates, and every device above it stays closed. It is not a property of any single breaker, it is a property of the pairing of devices, and it must be engineered, not assumed.

Why it fails

Two breakers in series both see the same fault current at the same moment. If their operating characteristics overlap in the current region the fault produces, the race is undefined, and large faults sit in the instantaneous region of both devices unless the upstream unit is deliberately configured otherwise. The classic failure modes we find in audits:

How a coordination study fixes it

A proper study models the network, utility fault level, transformers, cables, every protective device, and computes fault currents at each bus. Device time-current curves are then plotted in series pairs and settings chosen so that, at every credible fault current, a defined margin separates the downstream and upstream characteristics. The deliverable that matters is not the report; it is the settings schedule: device by device, pickup by pickup, applied at commissioning and recorded in the handover file.

A study that was never applied to the breakers is a fiction with a cover page. When we deliver a study with a panel, the settings are dialled in at FAT and witnessed, the schedule and the hardware leave the workshop already in agreement.

When full selectivity is not achievable

Sometimes physics wins, device ratings, fault levels or cost make total selectivity impossible at every level. The honest engineering answer is declared partial selectivity: state the current threshold up to which discrimination is guaranteed, confirm it covers the overwhelming majority of credible faults (most real faults are far below the bolted maximum), and let the client accept the residual risk knowingly rather than discover it in an outage.

Nuisance trips or an unverified hierarchy?Request a coordination study
Testing & Commissioning

The FAT Witness Checklist: What to Verify Before You Accept an LV Panel

HIKS STAR Engineering8 min read

A factory acceptance test is the single cheapest moment in a panel's life to find a problem. The same defect found on site costs ten times more; found after energisation, a hundred times. Yet many FATs are attended rather than witnessed, a walk around a closed board, a signature, lunch. Here is what a witness who intends to find problems actually checks.

Before you travel

Visual and mechanical, doors open

Electrical tests to witness live

TestWhat acceptance looks like
Insulation resistancePhase-phase, phase-N, phase-E; values recorded per circuit, consistent across phases, a single low outlier is a finding, not a rounding error
Dielectric (power frequency)Applied per IEC 61439-1 routine values with devices appropriately isolated; no flashover, no trip
Protective circuit continuityLow-resistance reading from earth bar to every door, plate and frame member, hinged parts through their bonding straps
Functional / controlEvery control sequence exercised: metering reads, lamps and annunciation, AMF/ATS cycles simulated end-to-end, interlocks proven
Protection settingsTrip unit settings match the coordination study schedule, read from the device, not from the paper
The one question that separates a real FAT from theatre: "show me a test failing." Ask the builder to demonstrate one protection trip live, a primary or secondary injection on one feeder proves the chain from sensor to mechanism actually works.

Before you sign

Every result recorded with the instrument serial number, every punch item written with a closure date, and the dossier, not a promise of one, in your hand or your inbox. At HIKS STAR the signed dossier is a release condition: the panel physically does not ship without it, and its contents live permanently behind the Panel Passport QR on the door.

Want our full FAT protocol template for your next project?Request the template
Design for GCC Conditions

Busbar Sizing and Temperature Rise at 50 °C: Why Catalogue Ratings Fail in the Gulf

HIKS STAR Engineering9 min read

A 2,500 A busbar system that performs faultlessly in a European plant room can run dangerously hot in a Gulf summer switchroom, while carrying exactly the current on its nameplate. The nameplate is not wrong. It was simply rated for a different planet.

The ambient assumption hiding in every rating

IEC 61439-1 verifies temperature rise against a reference ambient, a daily average of 35 °C with peaks to 40 °C. The permitted temperature rises (for example at terminals and accessible surfaces) are limits above that ambient. Put the same assembly in a 50 °C switchroom and every component starts its day 10-15 degrees closer to its limit: insulation ages faster, breaker thermal elements drift toward nuisance operation, and joint resistance, the silent killer, accelerates its slow rise.

What actually determines busbar capacity

Doing it properly for a 50 °C site

  1. State the design ambient in the specification, "50 °C switchroom, 55 °C peak" changes the design; silence changes nothing.
  2. Derate or verify: apply the OEM system's published derating factors for elevated ambient, or verify the specific configuration by calculation/test per the IEC 61439-1 design-verification routes. Rules of thumb are not verification.
  3. Engineer the room, not just the board: switchroom ventilation or cooling sized for the assembly's dissipated watts (every kW of losses is a kW of heat load) is cheaper than oversizing every bar.
  4. Instrument the risk away: for critical boards, specify joint temperature monitoring or a thermographic survey regime, annual imaging finds the failing joint years before it fails.
The cheapest busbar upgrade in the Gulf is a ventilation fan and a thermal camera. The most expensive is the one specified after the fire.
Specifying a board for a hot site?Get a verified thermal design
Critical Power

AMF vs ATS: Specifying Generator Changeover Without the Confusion

HIKS STAR Engineering8 min read

The two terms are used interchangeably in half the specifications we receive, and the gap between what was written and what was meant surfaces at the worst possible moment: the first real power failure.

Two functions, often one panel

ATS, Automatic Transfer Switch, is the switching function: the mechanism and interlocking that transfers the load between two sources safely, ensuring both can never feed the bus simultaneously. AMF, Automatic Mains Failure, is the brain: the controller that detects mains failure against set thresholds, commands the generator to start, supervises voltage and frequency until the set is stable, initiates the transfer, and manages the return, retransfer delay, generator cooldown run, and shutdown. An AMF panel therefore contains a transfer mechanism; a bare ATS assumes something else is managing the generator.

The specification gaps that cause failed outage tests

What a complete changeover specification states

  1. Sources, ratings and fault levels of both supplies
  2. Transfer type (open/closed/delayed) and permitted break time
  3. Full timing schedule with settable ranges
  4. Interlocking: mechanical + electrical, with proof at FAT
  5. Neutral switching arrangement, justified against the earthing system
  6. Controller functions: event log, comms to BMS, remote status
  7. Witnessed outage simulation at FAT, multiple full cycles, not one
Our own FAT standard for changeover panels is twenty consecutive simulated outage cycles under supervision. A changeover that works once proves nothing; the twentieth cycle is where a marginal relay or a loose start-signal terminal announces itself.
Specifying standby power for a critical facility?Talk to our engineers
Frequently Asked Questions

Straight answers to the questions we hear most.

And for anything specific to your project, drawings, sites, deadlines, the fastest answer is always a direct one: info@hiks.org or +971 52 249 5822.

What do you need from me to give a quotation?
A single-line diagram and a BOQ or load schedule gets you a firm technical quotation within two working days. If you don't have those yet, even a marked-up sketch and the project location is enough for us to start, send what you have to info@hiks.org and an engineer will tell you exactly what's missing, at no cost.
What are your typical lead times for LV panels?
Lead time depends on the component ecosystem specified, ratings and the form of separation, breaker deliveries, not our workshop, usually set the critical path. Share your target energisation date with us early and we'll confirm a realistic programme in the quotation, including options to compress it.
Which standards do you build and test to?
All assemblies are constructed and routine-verified to IEC 61439-1/-2, with the design basis declared against the OEM tested system in every quotation. Project-specific requirements, local authority, 50 °C ambient design, special forms, are captured at document review before we order material. Tell us your authority and specification and we'll confirm the compliance route for your project.
Can my consultant witness the factory acceptance test?
Yes, we insist on it. The FAT protocol is agreed with your consultant before testing starts, the test is conducted on calibrated instruments with traceable certificates, and the panel is released only against a signed dossier. Contact us to see a sample protocol for your panel type.
Do you supply components only, breakers, ACBs, MCCBs, accessories?
We do. Through our component supply service we source genuine ACBs, MCCBs, meters, relays and panel accessories from the major OEM ecosystems, each with certificates and serial traceability. Send us your list, even a photo of a nameplate for an obsolete unit, and we'll come back with availability and equivalents.
Which component brands can you build with?
We're a multi-brand assembler, Siemens, Schneider Electric, ABB, Eaton, Legrand, Socomec and others. Your panel is built on the ecosystem your specification calls for. If the specification is silent, we'll recommend options with the trade-offs explained, ask us.
Can you work on live sites, retrofits and upgrades without a full shutdown?
Yes, retrofit inside constrained shutdown windows is one of our core services. The answer for your site depends on the board's condition, separation form and switching arrangements, share photos and the existing SLD and we'll assess what can be done live, what needs a window, and how short that window can be.
Do you provide power system studies with the panel, or separately?
Both. Studies (load flow, short circuit, selectivity, arc flash, in ETAP) can accompany a panel order, in which case breaker settings are applied and witnessed at FAT, or be commissioned standalone for an existing installation. Tell us which situation you're in and we'll scope it.
What happens after handover if something goes wrong?
You call the engineer whose signature is on your FAT dossier, not a call centre, and every HIKS STAR panel carries its complete build record behind the Panel Passport QR on the door, so whoever responds sees your panel's history immediately. Breakdown response and annual maintenance contracts are available; ask us for AMC terms for your installation.
Do you serve projects outside the UAE?
Yes, we deliver from Dubai across the GCC: Saudi Arabia, Qatar, Oman, Bahrain and Kuwait. Logistics, site services and FAT arrangements differ by country, so tell us where your project is and we'll confirm the delivery approach in the quotation.
Question not here? It deserves an engineer's answer.Ask us directly